Three-phase induction electricity meter I699

Счетчик трехфазный индукционный И699

Three-phase induction electricity meter is approved to be used in the Republic of Belarus as a metering tool – type certificate № 5705, State list № RB 03 13 0910 09.

 Three-phase induction electricity meter (hereinafter - the meter) is a metering tool of the induction system, which serves to account active energy in three-phase four-wire AC circuits.


The meter is designed to work indoors at the temperatures range from minus 20 to plus 40 ° C and the relative humidity of 80% at 25 ° C in the absence of corrosive gases and vapors in the air.

 The meter is not intended to be used in explosive areas.

 Main technical data and specifications

1. Meters SA4-I699, SA4U-I699 comply with TU RB 07514363.042-99, STB GOST 52320-2007, STB GOST R 52321-2007.

 2. Meters modifications should match the table.

 

Meter type

Modification

Gear ratio, r / kWt × h

Current 1b(rated), A

Current Imax, A

Overall dimensions, mm

Setting dimensions, mm

SA4U-I699

 

OTIB.411119.026-09

450

5

6,25

282х173х127

Vert. - 214 ± 1

Hor. - 155 ± 1

SA4U-I699

 

OTIB.411119.026-01-10

225

10

20

282х173х127

Vert.- 214 ± 1

Hor. - 155 ± 1

SA4U-I699

 

OTIB.411119.026-02-11

150

10

40

282х173х127

Vert.- 214 ± 1

Hor. - 155 ± 1

SA4U-I699

OTIB.411119.028-01

40

50

100

295х173х127

Vert.- 214 ± 1

Hor. - 155 ± 1

SA4U-I699

OTIB.411119.028-02

60

20

100

295х173х127

Vert.- 214 ± 1

Hor. - 155 ± 1

Note: meter OTIB. 411119.026-09; -10; -11; are produced with a stopper preventing the meter running backwards.

With reference to the accuracy of electricity accounting the meter belongs to the accuracy class 2.0 according to STB GOST R 52320-2007, STB GOST R 52321-2007.

The nominal line voltage is 380 V, rated frequency - 50 Hz.

The total power consumed by voltage circuit at rated voltage and rated frequency does not exceed 6.0 V × A, active - not more than 1.5 Wt.

The total power consumed by current circuit at rated voltage and rated frequency does not exceed 6.0 V × A (for meters-SA4 I699 with a current load of 50 - 100 A 20-100 A and no more than 2.0 V × A).

The meters SA4-I699 are connected directly, with SA4U-I699 – are used all kinds of current transformers.

The meter weight is not more than 3.7 kg.

The average time of service is at least 32 years.

Completeness:

The package includes:

  • meter with a lid - 1 pc
  • manual - 1 copy
  • package - 1 pc

A consumer multipack is allowed without unit packages.

The meter installation, functioning, maintenance

  • The meter should be installed according to the "Rules for Electrical Installation" (SEP).
  • The meter should be operated in accordance with the TAP 181-2009 "Rules of technical operation of electrical installations of consumers."
  • The meter should be set up in full compliance with its nominal data and schema located on the inner side of the terminal cover.
  • Installation, dismantling, stripping, repairs, calibration and marking should only be carried out by the specially authorized organizations and individuals according to the rules for installation of electrical installations, by observing the phase sequence.
  • The meter measures electricity in kilowatt hours.
  • The transformation ratio of instrument transformers that is not accounted by the counting mechanism are shown on an incremental plate attached to the lid of the terminal block. The energy value on the primary winding of the transformer in this case is determined by multiplying the reading counter mechanism by a coefficient K.
  • Counting mechanism window, which indicates tenths of a kilowatt-hour, is bordered with black, and separated by a comma. Tenth of kilowatt-hours are not shown in the counting mechanism of meters 10-40 A and 50-100 A.
  • A mandatory state verification of the meter is required once in 4 years STB 8003-93.
  • Meters calibration should be performed in accordance with GOST 8.259-2004.
  • Readings on the metering mechanism is the result of the meter calibration at the plant, rather than evidence of its use.

Shipment and storage 

  1. The meter shipment should only be performed in a closed transport (railway cars, containers, closed vehicles, the holds of ships, etc.) under the conditions of shaking with an acceleration of no more than 30 m /s2 at a frequency of strokes from 80 to 120 per minute at the temperature from minus 50 to plus 50 º C and relative humidity of 98% at 25 º C.
  2. The meter before setting into operation should be stored in the transport and consumer package.
  3. The meter should be kept indoors, where temperatures can range from 5 to 40 º C, relative humidity does not exceed 80% at 25 º C in the absence of corrosive vapors and gases.

Manufacturer's warranty 

  1. The manufacturer ensures the meter compliance with the requirements of technical conditions (TU), STB GOST R 52320-2007, STB GOST R 52321-2007 under the terms of operation, transportation, storage, installation, dismantling and preservation of the verification seal. 
  2. Warranty period is 24 months from the date of the meter setting into operation or from the date of sale – for the meter that is sold by the retail trade system. Warranty period is 24 months from the date of the meter manufactured. 
  3. The warranty does not apply to the meter: 
  • with broken seals of  OTK (quality control department)  and state verification officer;
  • with mechanical damages of the hull;
  • without the data about the meter assembling and disassembling in the meter passport that has been already in use;
  • with violation of the terms of transportation, usage, storage, installation and dismantling.
  1. The meter, which during the warranty period failed to comply with the requirements of TU is to be returned to the manufacturer for rechecking and finding out the reasons for its failure. The defective meter is to be replaced or refurbished by the manufacturer if the customer has been observing the terms of usage, transportation, storage, installation, dismantling and seals verification. If the mentioned terms are violated the repairs are to be made at the expense of the consumer.

Spare parts for the electricity meter I699


1 2 3 4 5
Axis with disks IBYASH.411119.000
Saddle 5PТ.262.018
Spring 8PT.281.016
Bearing 5PT.263.006
Ball H 1.588-3 GOST 3722-81
6 7 8 9 10
Set of current loops SA – I699 (10 – 40 A)
Jumper 8PТ.585.029
Screw OTIB.758161.004
Bar 8PT.150.052  Set of current coil SA4U – I699(5A)
11 12 13 14 15
Plate IBYASH.754342.005
Set of current coil SA4 – I699(10 – 20 A)
Magnet OTIB.301524.028 – 01
Current coil frame 8PT.732.004
Cover OTIB.305142.041 – 01
11 12 13 14 15
Screw  М4-6gх35.36.016 SТPG 6-93-89
Terminal cover 8PT.315.013
Terminal cover OTIB.735411.006
Base OTIB.411119.022
Base OTIB.411119.029

 

Общие запасные части для счётчиков электрической энергии однофазных (СО-И496) и трёхфазных (И699) индукционных

1a 2a 3a 4a 5a
Voltage coil IBYASH. 685442.000
Ring -01(to metering system)

Current loop cover OTIB.754529.009 (OTIB.754529.010)

Wheel 8PT.240.086
Wheel 8PT.240.085
6a 7a 8a 9a 10a
Screw М4-6gх14.36.016 STPG 6-93-89
Screw М4-6gх22.36.016 STPG 6-93-89
Flexible string IBYASH. 745361.000
 Short-circuited aluminum loop 8PG.546.001 Carton disk OTIB.711141.061
11a 12a 13a 14a 15a
 Aluminum disk 8PG.950.015  Pin 8PT.206.038  Wedge 8PT.194.008
Plastic nut 8PG.946.005
Actuator 8PG.448.000-01
16a 17a 18a 19a  

Set of cores (core 5PT.619.005, jumper 5PT.585.000, core 5PT.619.004)
 

Voltage core 5PT.619.004
Current core 5PT.619.005
 Jumper 5PT.585.016
 
ОАО "Брестский электромеханический завод" 2019 год. Все права защищены.
При использовании материалов сайта ссылка на bemzbrest.by обязательна!

logo